Inta 28mm Anti-freeze Valve 28mm connections – ZERO28
The Inta Zero is a unique anti-freeze valve designed and engineered to protect heat pump systems that are operating with water. Designed to discharge when the system water temperature drops to 3°C, preventing ice from forming in the heat pump circuit that could cause breakdown or costly damage to the system.
- Max Inlet Pressure (static): 10 Bar
- Medium: Water
- Sensitivity: +/-1°C
- Opening Temperature: 3°C
- Closing Temperature: 4°C
- Valve Body: UNI EN 12165 CW617N
- Spring: Stainless Steel
- Internal Parts: UNI EN 12164 CW617N
- Internal Seals: EPDM PEROX
- Working Temperature Range: 0 – 65°C
- Ambient Temperature Range: -30 – 60°C
- Kv: 64m³/h
- Max Discharge Flow Rate @ 3 Bar: 1.5 L/H
Insulating
The patented Inta Zero Anti-Freeze Valves have been specifically designed to quickly and accurately react to the water temperature in the heat pump circuit and do not need the influence of the ambient temperature to operate.
Building regulations Part L states that all external fittings on an Air Source Heat Pump System must be fully insulated to reduce heat loss and maintain system efficiency. Inta Zero Anti-Freeze Valves will still maintain correct operation and discharge the water at the same temperature even when a system is correctly insulated.
The Inta Zero Anti-Freeze valves have been Independently tested using a controlled Ambient Temperature between -1°C to 1°C and starting water temperature 10°C to demonstrate the possibility of insulating the Inta Zero Valve without affecting the performance:
Without Insulation:
- Water Discharge Temperature = 2.49°C
- Time taken to begin discharge = 1 hour 4mins
With Insulation:
- Water Discharge Temperature = 2.03°C
- Time taken to begin discharge = 4hour 3mins
Warning!
If the Inta Zero valves are insulated, then due care must be taken to ensure that all external pipework and fittings are fully and appropriately insulated and sealed. Failure to do so could prevent the proper operation of the Zero valve resulting in colder areas of a system being damaged by freezing. The Anti-vacuum valve must be kept clear at all times (inspected on annual service).